Below freezing, water trapped in irrigation pipes does what water always does: expands by about 9% and splits whatever holds it. The damage doesn't show up until spring start-up, and by then you're replacing cracked PVC, a split backflow preventer, a brass shut-off valve, and a handful of zone valves and nozzle bodies. Winterizing the system before the first hard freeze is one afternoon of work; not winterizing it is a four-figure repair.
This guide covers the two methods homeowners use to clear water from a Hunter sprinkler system before winter:
The guide also covers the two things every system needs regardless of method: protecting the backflow preventer (the most freeze-sensitive component above grade) and setting the controller so the system doesn't try to run during the freeze.
Before you start, identify what Hunter components you have. The procedure is the same across the Hunter rotor + spray family (PGP, I-20, MP Rotator, Pro-Spray, PRS30, PRS40); the controller step varies by model (X-Core, Pro-HC, HCC, X2 — see the Hunter brand page).
Three questions pick the method for you:
How the answers map:
When in doubt, blow out. Manual drain underperforms in conditions homeowners often misread.
The manual drain method works the system from the supply side downward. Sequence matters: shutting the water off before opening the drains gives gravity a clean path; opening drains first just makes a puddle.
The first sign of a partial drain is a zone that still produces water when you open its heads by hand 30 minutes after the sequence. If a zone still has water in it, the lateral has no slope at that location, or a drain valve is blocked. Do not declare the system winterized. Either follow up with a blow-out for that zone, or accept the freeze risk knowingly.
The blow-out method works on any system regardless of slope or drain-valve presence, which is why it's the standard. The trade-off is risk: pushing air through irrigation components at the wrong PSI cracks heads, melts nozzle seals, and ruptures pipes. The numbers below are not suggestions — they're Hunter's published limits and the difference between a winterized system and a broken one.
Per Hunter Industries' winterization guidance:
The blow-out pressure should also stay below the maximum operating pressure of the lowest-rated component on the zone. If your zone has a 50 PSI-rated drip regulator on it, that's your ceiling, not the 80 PSI pipe rating.
The spec is CFM (cubic feet per minute), not PSI. Hunter recommends an 80–100 CFM compressor for any mainline of 2" or less — typical residential. That is a tow-behind rental compressor, not a garage 5-gallon. A small compressor that hits 80 PSI on the gauge but only delivers 5 CFM cannot move enough air through the zone to push the water out; the line pressurizes, the heads pop up dry, and the water stays in the pipe.
Rent the right compressor or hire it out. The "I'll just use what I have" instinct is what cracks pipes here.
The backflow preventer sits above grade between the water supply and the irrigation system, exposed to ambient air. It is the single most likely component to split in a freeze, and the most expensive non-controller component to replace. Treat it as a separate procedure regardless of which clearing method you used.
Wrap the device in an insulated backflow bag sized to your device. The small BFA1HBBG insulated backflow bag ($20.99) fits most 3/4" and 1" residential PVBs and double-checks. For larger residential or light-commercial devices, the 24" × 24" insulated bag ($58.99) is the next size up. Insulation alone does not stop a hard freeze on an undrained device — drain first, insulate second.
If you're replacing a freeze-failed backflow this season, Febco's T765HBV PVB (FEB-58-1135) is the in-stock model with a built-in freeze sensor for systems that need to detect impending freeze automatically — a one-time upgrade that catches the case where someone forgets to winterize.
The controller does not need to be removed or unplugged for winter. Leave it powered so the internal battery doesn't drain and the programming survives. What you change is the run schedule.
A wireless rain/freeze sensor (e.g. the Rain Bird WR2RFC-48) wired to the controller's sensor terminals provides a second layer of automation: if a shoulder-season freeze hits while the system is still active, the sensor cuts irrigation until temperatures recover. Useful where shoulder seasons are unpredictable; not a substitute for the winterization procedure itself.
If you're working through the rest of your seasonal maintenance: